The BMXMSP0200 is a PTO (pulse train output) module of the Schneider Electric Modicon X80 range, the common I/O platform used with the Modicon M340 and M580 Programmable Automation Controllers. It provides two independent pulse train outputs for the position and speed control of servo drives and stepper drives, and it is fitted in a standard module slot of a Modicon X80 rack. Because the two channels are independent, one module can drive two axes, or two mechanically linked axes that must be synchronised from the same controller cycle.
Each channel delivers a pulse train up to 200 kHz on a 24 V DC output, with output voltage limits of 19...30 V. The module also provides two 24 V DC auxiliary outputs rated 50 mA, used for enabling the drive or for a brake. Maximum leakage current is 0.05 mA at state 0, residual voltage is 0.15 V at state 1, and output response time is 1.2...1.5 ms on appearance and on disappearance. Outputs are protected against overload and short circuit by a current limiter and an electronic circuit breaker, and against reverse polarity by a reverse mounting diode on the output.
Four discrete auxiliary inputs complete the channel functions: Drive_Ready&Emergency and Counter_in_Position accept sink or source wiring to IEC 61131-2 type 3, while Origin and Proximity&LimitSwitch are sink inputs to the same type. Inputs are 24 V DC with an input current of 4.3 mA, state 1 is guaranteed above 11 V and state 0 below 5 V, and they accept 2-wire or 3-wire proximity sensors from 19.2 to 30 V to IEC 947-5-2. Response time is below 200 µs for the position completed and drive ready inputs and below 60 µs for the origin and proximity inputs, which is what allows homing and limit-switch stops to stay inside the controller cycle.
The achievable output frequency depends on the cable and on the receiving circuit, which is the point to check when the drive is more than a few metres away: 200 kHz with a USIC signal converter and a VW3M8210R05 cable shorter than 0.5 m, 100 kHz with the normal source input circuit shorter than 5 m, and 200 kHz with RS422 compatible circuits shorter than 10 m. A twisted pair cable is required between the module and the drive. When the PLC is set to STOP, the pulse outputs keep their state unless the Drive_Ready input is driven to 0 by an output module such as the BMXDRA0805 or BMXDRA1605.
The module draws 35 mA at 24 V DC and supplies its preactuators with 150 mA typical and 200 mA maximum at 3.3 V DC. There is no insulation between the two channels, insulation between primary and secondary is 1500 Vrms, and insulation resistance is above 10 MOhm. Wiring is made on two 28-pin connectors, so two 28-pin terminal blocks are needed. Front panel signalling covers module running (RUN, green), external I/O fault (red), internal fault (ERR, red), download (DL, green) and eight channel status LEDs per channel. Operating ambient temperature is −25...70 °C without derating. The module is certified CE, UL, CSA, RCM, EAC, Merchant Navy, ATEX zone 2/22 and IECEx zone 2/22, is suitable for hazardous location class I division 2, and meets IEC 61131-2, IEC 61010-2-201, UL 61010-2-201, CSA C22.2 No 61010-2-201, IACS E10, IEC 61000-6-5 interface type 1 and type 2, IEC 61850-3 location G and IEC 60079-0. Net weight is 0.145 kg; packing unit 1 is one piece measuring 11.7 cm by 11.5 cm by 5.4 cm and weighing 147 g. Warranty is 18 months.
| Characteristic | Value |
|---|---|
| Brand | Schneider Electric |
| Range of product | Modicon X80 |
| Product or component type | PTO module |
| Number of channels | 2 |
| Number of inputs | 4 |
| Discrete input type | Current sink origin input, IEC 61131-2 type 3; current sink proximity input and limit switch input, type 3; current sink or source counter in position input, type 3; current sink or source drive ready, emergency input, type 3 |
| Input compatibility | 2-wire/3-wire proximity sensor 19.2...30 V, IEC 947-5-2 |
| Input voltage | 24 V DC |
| Input current | 4.3 mA |
| Voltage state 1 guaranteed | >= 11 V |
| Current state 1 guaranteed | >= 2 mA |
| Voltage state 0 guaranteed | 5 V |
| Current state 0 guaranteed | <= 1.5 mA |
| Response time — inputs | < 200 µs for position completed input and drive ready input; < 60 µs for origin input and proximity input |
| Number of outputs | 1 pulse output per channel (2 channels); 2 auxiliary outputs |
| Output compatibility | Signal converter (USIC) RS422, 7 mA input; source input, 5 V to 24 V |
| Output frequency | 200 kHz < 0.5 m with USIC and VW3M8210R05; 100 kHz < 5 m with the normal source input circuit; 200 kHz < 10 m with RS422 compatible circuits |
| Output voltage | 24 V DC (limits 19...30 V) |
| Discrete output current | 50 mA |
| Maximum leakage current | 0.05 mA at state 0 |
| Residual voltage | 0.15 V at state 1 |
| Response time — outputs | 1.2...1.5 ms on appearance; 1.2...1.5 ms on disappearance |
| Output overload protection | By current limiter and electronic circuit breaker |
| Output short-circuit protection | By current limiter and electronic circuit breaker |
| Reverse polarity protection | By reverse mounting diode on output; integrated on input |
| Current consumption | 35 mA at 24 V DC; preactuator 150 mA typical and 200 mA maximum at 3.3 V DC |
| Insulation between channels | Not insulated |
| Insulation between primary and secondary | 1500 Vrms |
| Insulation resistance | > 10 MOhm |
| Local signalling | 1 green LED RUN; 1 red LED I/O fault; 1 red LED ERR; 1 green LED DL; 8 green LEDs CH00; 8 green LEDs CH01 |
| Electrical connection | 2 connectors, 28 pins |
| Module format | Standard |
| Height | 100 mm |
| Depth | 140 mm with removable terminal block |
| Net weight | 0.145 kg |
| Ambient air temperature for operation | −25...70 °C |
| Derating factor | Without |
| Product certifications | CE, UL, CSA, RCM, EAC, Merchant Navy, ATEX zone 2/22, IECEx zone 2/22 |
| Hazardous location | Class I division 2 |
| Standards | IEC 61131-2; IEC 61010-2-201; UL 61010-2-201; CSA C22.2 No 61010-2-201; IACS E10; IEC 61000-6-5 interface type 1 and type 2; IEC 61850-3 location G; IEC 60079-0 |
| Directives | 2014/35/EU (low voltage); 2014/30/EU (EMC); 2014/34/EU (ATEX) |
| Packing unit 1 | 1 PCE, 11.7 x 11.5 x 5.4 cm, 147 g |
| Warranty | 18 months |