The BMXCPS2010 is a power supply module for the Modicon X80 platform, the common rack system of the Modicon M340 and M580 controllers. It sits in the rack and feeds the modules plugged onto the backplane: the processor, the communication modules and the I/O modules. It is a DC input module, which is the point that has to be settled before anything else, because the AC input version of the same family looks and mounts the same way and is fed from 100 to 240 V AC mains. This one takes an existing 24 V DC supply from the cabinet; connecting it to mains will destroy it.
The primary side is 24 V DC, isolated, with an operating range of 18 to 31.2 V and an input current of 1 A at 24 V. Inrush current is 30 A, with an I²t on activation of 0.6 A²s and an I t of 0.15 A s, which is what decides the rating of the upstream breaker rather than the steady-state current. Immunity to microbreaks is 1 ms, so a short dip on the 24 V supply does not drop the rack. Supply cable length is limited to 20 m with 1.5 mm² copper and 30 m with 2.5 mm², and that limit should be checked against the panel layout rather than assumed.
Two outputs are generated on the secondary side. The 24 V DC output delivers 0.7 A, 16.8 W, for the I/O modules and the processor supply, and the 3.3 V DC output delivers 2.5 A, 8.3 W, for the I/O module logic. Both are derived from the same isolated primary, so the rack is fed from a single 24 V source instead of separate supplies per group of modules. The secondary 24 V output also carries the sensor supply, which is why the protection on that rail matters: overload, overvoltage and short-circuit protection are all implemented on the secondary circuit, while the primary circuit relies on an internal fuse that cannot be accessed or replaced from outside.
Diagnostics are deliberately simple, because this is a module nobody wants to troubleshoot. One green LED confirms that the backplane voltage is present, a RESET push-button performs a cold restart of the rack, and a 2-pin connector carries an alarm relay contact that can be wired to the panel or to the controller. The line side lands on a 5-pin connector for the supply, protective earth and the 24 V DC sensor input. Insulation resistance is 10 MOhm or more both primary to ground and primary to secondary, and dielectric strength is 1500 V on both paths. Power dissipation is 8.5 W and MTBF is 4,886,000 hours.
Check the backplane before ordering: this module is declared not compatible with the BMEXBP..02 range, so a rack from that family needs a different supply reference. The module is one slot wide at 32 mm, 100 mm high and 140 mm deep with the removable terminal block fitted (160 mm with an FCN connector), and it is IP20, so it belongs inside an enclosure. Operating ambient is 0 to 60 °C, storage is -40 to 85 °C, relative humidity is 5 to 95 % at 55 °C without condensation, operating altitude is 2000 m without derating and up to 5000 m with a derating factor. Vibration resistance is 3 gn and shock resistance 30 gn. The module carries the TC protective treatment and is declared to the low voltage directive 2014/35/EU and the EMC directive 2014/30/EU. Net weight is 0.29 kg; one piece is packed in a 155 x 130 x 153 mm carton of 0.478 kg. Country of origin: France.
| Characteristic | Value |
|---|---|
| Range of product | Modicon X80 |
| Product or component type | Power supply module |
| Backplane compatibility | Not compatible with BMEXBP..02 |
| Primary voltage | 24 V DC, isolated |
| Supply circuit type | DC |
| Primary voltage limit | 18...31.2 V |
| Input current | 1 A at 24 V |
| Inrush current | 30 A at 24 V |
| I²t on activation | 0.6 A²s at 24 V |
| It on activation | 0.15 A s at 24 V |
| Secondary power, 24 V | 16.8 W at 24 V DC (I/O modules and processor) |
| Secondary power, 3.3 V | 8.3 W at 3.3 V DC (I/O module logic) |
| Current at secondary voltage | 0.7 A at 24 V DC, 2.5 A at 3.3 V DC |
| Protection type | Internal fuse not accessible (primary); overload, overvoltage, short-circuit protection on secondary 24 V sensor supply |
| Status LED | 1 green LED, backplane voltage OK |
| Control type | RESET push-button, cold restart |
| Electrical connection | 1 x 2-pin connector (alarm relay); 1 x 5-pin connector (line supply, protective earth, 24 V DC sensor input) |
| Maximum cable distance | 20 m with 1.5 mm² copper; 30 m with 2.5 mm² copper |
| Insulation resistance | ≥ 10 MOhm primary/ground, ≥ 10 MOhm primary/secondary |
| Dielectric strength | 1500 V primary/ground, 1500 V primary/secondary |
| Immunity to microbreaks | 1 ms |
| Maximum power dissipation | 8.5 W |
| MTBF reliability | 4,886,000 h |
| Dimensions (H x W x D) | 100 x 32 x 140 mm (160 mm with FCN connector) |
| Degree of protection | IP20 |
| Protective treatment | TC |
| Directives | 2014/35/EU (low voltage), 2014/30/EU (EMC) |
| Vibration resistance | 3 gn |
| Shock resistance | 30 gn |
| Ambient air temperature for operation | 0...60 °C |
| Ambient air temperature for storage | −40...85 °C |
| Relative humidity | 5...95 % at 55 °C without condensation |
| Operating altitude | 0...2000 m; 2000...5000 m with derating factor |
| Country of origin | France |
| Net weight | 0.29 kg |
| Packing unit weight | 0.478 kg |
| Packing unit dimensions | 155 x 130 x 153 mm |