Welcome to Dongguan Gexu Automation Equipment Co., Ltd

ALL CATEGORIES

BMXCPS2000 - Power Supply Module, 100-240 V AC Input, 20 W, Modicon X80

Product type: Power supply module  |  Range: Modicon X80  |  Input: 100...240 V AC, 50/60 Hz, 0.61 A at 115 V / 0.31 A at 240 V  |  Outputs: 24 V DC 0.7 A (16.8 W) + 24 V DC 0.45 A sensor supply (10.8 W) + 3.3 V DC 2.5 A (8.3 W)  |  Width: 32 mm  |  Backplane: not compatible with BMEXBP..02

The BMXCPS2000 is a power supply module for the Modicon X80 platform, the common rack system of the Modicon M340 and M580 controllers. It sits in the rack and feeds everything plugged onto the backplane: the processor, the communication modules and the I/O modules. This is the mains version, taking 100 to 240 V AC directly from the cabinet supply. Settle the input side first, because the DC input version of the same family, the BMXCPS2010, is identical in width, height, depth and mounting: feeding this one with 24 V DC will simply not start it, and feeding the 2010 with mains will destroy it.

The primary side accepts 100 to 240 V AC at 50 or 60 Hz, with a permitted range of 85 to 264 V and a network frequency window of 47 to 63 Hz, so it rides through the usual sag on a loaded panel. Input current is 0.61 A at 115 V and 0.31 A at 240 V, with apparent power of 0.07 kVA. Inrush current is the number that sizes the upstream breaker, not the steady-state current: 30 A at 120 V and 60 A at 240 V, with an I²t on activation of 12 A²s and an It of 0.06 A s at 240 V. Immunity to microbreaks is 1 ms. Because the module is fed from mains, the protective earth on the 5-pin line connector is not optional.

Three rails are generated on the secondary side. The 24 V DC output delivers 0.7 A, 16.8 W, for the I/O modules and the processor supply; a separate 24 V DC sensor supply delivers 0.45 A, 10.8 W; and the 3.3 V DC output delivers 2.5 A, 8.3 W, for the I/O module logic. All three come from the same isolated primary, so one mains feed covers the whole rack. Overload, overvoltage and short-circuit protection sit on the secondary circuits, while the primary relies on an internal fuse that cannot be reached or replaced from outside, which is why a fault on the mains side means replacing the module rather than the fuse. Insulation resistance is 100 MOhm or more primary to ground and primary to secondary, and dielectric strength is 2300 V on the sensor supply path and 1500 V on the other primary-to-secondary paths and primary to ground.

Diagnostics are deliberately plain. Two green LEDs report backplane voltage present and sensor voltage present, a RESET push-button performs a cold restart of the rack, and a 2-pin connector carries an alarm relay contact that can be wired to the panel or back to the controller. The line side lands on a 5-pin connector for the supply, protective earth and the 24 V DC sensor input. Power dissipation is 8.5 W and MTBF is 4,638,000 hours at 40 °C, so this is not a part that should be failing on its own.

Check the backplane before ordering: this module is declared not compatible with the BMEXBP..02 range, so a rack from that family needs a different supply reference. It is one slot wide at 32 mm, 100 mm high and 140 mm deep with the removable terminal block fitted (160 mm with an FCN connector), and it is IP20, so it belongs inside an enclosure. Operating ambient is 0 to 60 °C, storage is -40 to 85 °C, relative humidity is 5 to 95 % at 55 °C without condensation, operating altitude is 2000 m without derating and up to 5000 m with a derating factor. Vibration resistance is 3 gn and shock resistance 30 gn. The module carries the TC protective treatment and is declared to the low voltage directive 2014/35/EU and the EMC directive 2014/30/EU. Net weight is 0.3 kg; one piece is packed in a 164 x 154 x 135 mm carton of 0.481 kg.

Specifications

Characteristic Value
Range of product Modicon X80
Product or component type Power supply module
Rated power 20 W
Backplane compatibility Not compatible with BMEXBP..02
Primary voltage 100...240 V AC
Supply circuit type AC
Primary voltage limit 85...264 V
Network frequency 50/60 Hz, limits 47...63 Hz
Input current 0.61 A at 115 V; 0.31 A at 240 V
Apparent power 0.07 kVA
Inrush current 30 A at 120 V; 60 A at 240 V
I²t on activation 12 A²s at 240 V
It on activation 0.06 A s at 240 V; 0.03 A s at 120 V
Secondary power, 24 V I/O and processor 16.8 W at 24 V DC, 0.7 A
Secondary power, 24 V sensor supply 10.8 W at 24 V DC, 0.45 A
Secondary power, 3.3 V logic 8.3 W at 3.3 V DC, 2.5 A
Protection type Internal fuse not accessible (primary); overload, overvoltage, short-circuit protection on secondary circuits
Status LED 1 green LED backplane voltage OK; 1 green LED sensor voltage
Control type RESET push-button, cold restart
Electrical connection 1 x 2-pin connector (alarm relay); 1 x 5-pin connector (line supply, protective earth, 24 V DC sensor input)
Insulation resistance ≥ 100 MOhm primary/ground, ≥ 100 MOhm primary/secondary
Dielectric strength 2300 V primary/secondary (sensor supply); 1500 V primary/secondary (I/O logic, I/O and processor); 1500 V primary/ground; 500 V 24 V sensor output/ground
Immunity to microbreaks 1 ms
Maximum power dissipation 8.5 W
MTBF reliability 4,638,000 h
Dimensions (H x W x D) 100 x 32 x 140 mm (160 mm with FCN connector)
Degree of protection IP20
Protective treatment TC
Directives 2014/35/EU (low voltage), 2014/30/EU (EMC)
Vibration resistance 3 gn
Shock resistance 30 gn
Ambient air temperature for operation 0...60 °C
Ambient air temperature for storage −40...85 °C
Relative humidity 5...95 % at 55 °C without condensation
Operating altitude 0...2000 m; 2000...5000 m with derating factor
Net weight 0.3 kg
Packing unit weight 0.481 kg
Packing unit dimensions 164 x 154 x 135 mm
Warranty 18 months