The BMXCPS2000 is the standard power supply module of the Schneider Electric Modicon X80 range, fitted in the power supply slot of a Modicon X80 rack. It converts a 100...240 V AC supply into the secondary voltages used by the rack: 24 V DC for the sensor supply, 24 V DC for the I/O module and processor supply, and 3.3 V DC for the I/O module logic supply. Total output power is 20 W.
On the primary side the module accepts 100...240 V AC at 50/60 Hz, with an operating range of 85...264 V and network frequency limits of 47...63 Hz. Input current is 0.61 A at 115 V and 0.31 A at 240 V, apparent power is 0.07 kVA, and inrush current is limited to 30 A at 120 V and 60 A at 240 V with an I²t on activation of 12 A².s at 240 V. The primary circuit is protected by an internal fuse that is not accessible from outside. A 2-pin connector is provided for the alarm relay.
The secondary side is split into three outputs. The 24 V DC sensor supply delivers 10.8 W at 0.45 A, the 24 V DC I/O and processor supply delivers 16.8 W at 0.7 A, and the 3.3 V DC logic supply delivers 8.3 W at 2.5 A. Each output is protected against overload, overvoltage and short circuit, and maximum power dissipation is 8.5 W. Immunity to microbreaks is 1 ms. Two green LEDs show rack voltage OK and sensor voltage, and a RESET push-button allows a cold restart.
Field wiring is brought out on a 5-pin connector carrying the line supply, protective earth and the 24 V DC sensor input. Insulation resistance is at least 100 MOhm between primary and ground and between primary and secondary. Dielectric strength is 1500 V between primary and the logic and I/O secondary circuits, 2300 V between primary and the sensor supply, 1500 V between primary and ground, and 500 V between the 24 V sensor output and ground. The module is delivered with TC protective treatment and is rated IP20 for mounting inside an enclosure, with vibration resistance of 3 gn and shock resistance of 30 gn.
Operating ambient temperature is 0...60 °C and storage temperature is −40...85 °C, with relative humidity of 5...95 % at 55 °C without condensation. Operating altitude is 0...2000 m, and 2000...5000 m with a derating factor. The module complies with the low voltage directive 2014/35/EU and the EMC directive 2014/30/EU. Height is 100 mm and depth is 140 mm, and net weight is 0.3 kg. Packing unit 1 is one piece measuring 16.4 cm by 15.4 cm by 13.5 cm and weighing 481 g. Warranty is 18 months.
| Characteristic | Value |
|---|---|
| Brand | Schneider Electric |
| Range of product | Modicon X80 |
| Product or component type | Power supply module |
| Backplane compatibility | Not compatible with BMEXBP..02 |
| Primary voltage | 100...240 V AC |
| Primary voltage limit | 85...264 V |
| Supply circuit type | AC |
| Network frequency | 50/60 Hz |
| Network frequency limits | 47...63 Hz |
| Apparent power | 0.07 kVA |
| Input current | 0.61 A at 115 V; 0.31 A at 240 V |
| Inrush current | 30 A at 120 V; 60 A at 240 V |
| I²t on activation | 12 A².s at 240 V |
| It on activation | 0.06 A.s at 240 V; 0.03 A.s at 120 V |
| Secondary power | 10.8 W 24 V DC sensor supply; 16.8 W 24 V DC I/O module and processor supply; 8.3 W 3.3 V DC I/O module logic supply |
| Current at secondary voltage | 0.45 A at 24 V DC (sensor); 0.7 A at 24 V DC (I/O and processor); 2.5 A at 3.3 V DC (logic) |
| Maximum power dissipation | 8.5 W |
| Protection type | Internal fuse not accessible (primary circuit); overload, overvoltage and short-circuit protection (secondary circuits) |
| Status LED | 1 green LED for rack voltage OK; 1 green LED for sensor voltage |
| Control type | RESET push-button for cold restart |
| Electrical connection | 1 x 2-pin connector (alarm relay); 1 x 5-pin connector (line supply, protective earth, 24 V DC sensor input) |
| Insulation resistance | >= 100 MOhm primary/ground; >= 100 MOhm primary/secondary |
| Dielectric strength | 1500 V primary/secondary (logic supply); 1500 V primary/secondary (I/O and processor supply); 2300 V primary/secondary (sensor supply); 1500 V primary/ground; 500 V 24 V sensor output/ground |
| Immunity to microbreaks | 1 ms |
| MTBF reliability | 4,638,000 h |
| Height | 100 mm |
| Depth | 140 mm |
| Net weight | 0.3 kg |
| IP degree of protection | IP20 |
| Protective treatment | TC |
| Vibration resistance | 3 gn |
| Shock resistance | 30 gn |
| Ambient air temperature for operation | 0...60 °C |
| Ambient air temperature for storage | −40...85 °C |
| Relative humidity | 5...95 % at 55 °C without condensation |
| Operating altitude | 0...2000 m; 2000...5000 m with derating factor |
| Directives | 2014/35/EU (low voltage); 2014/30/EU (EMC) |
| Packing unit 1 | 1 PCE, 16.4 x 15.4 x 13.5 cm, 481 g |
| Warranty | 18 months |