Welcome to Dongguan Gexu Automation Equipment Co., Ltd

ALL CATEGORIES

171CCS78000 - M1/M1E Processor Adaptor, Modbus, 20 MHz

Product type: M1/M1E Processor Adaptor  |  Range: Modicon Momentum  |  Processor: x86, 20 MHz  |  Memory: 256 kB flash / 64 kB RAM  |  Ports: 1 RS232C + 1 RS485, Modbus  |  Supply: 5 V DC via I/O base

The 171CCS78000 is an M1/M1E processor adaptor for the Modicon Momentum automation platform. It is not a complete controller on its own: it clips onto the top of a Momentum I/O base and turns that base into a working controller with local discrete and register I/O processing. The I/O base supplies its operating power and carries the field terminals, so this part is ordered either as a replacement for a failed adaptor or together with the base that matches the application.

The processor is x86 based, running at 20 MHz with a 16-bit word length. Program memory is 2.4 kB LL984 and data memory is 2 kB, backed by 256 kB of flash and 64 kB of RAM. Execution time is 1 ms for 1 K instructions. The adaptor handles up to 2048 discrete inputs and 2048 discrete outputs, and the same capacity applies to register I/O. The I/O limit is local I/O on Modbus, which is what defines the size of the station this adaptor can drive.

Communication is Modbus only, over two physical ports: one non-isolated RS232C port and one RS485 port. This distinction matters when ordering. The reference is often described as "2 Modbus" and some listings render it as two RS485 ports, but the hardware is one RS232C plus one RS485, so confirm the cabling before you buy. Both ports are used for programming, for HMI connection and for communicating with drives and meters.

The adaptor takes 5.0 V DC +/-5 % from the Momentum I/O base. It has no AC input and no separate power supply terminal, so nothing is wired to a 230 V or 24 V source on this part. If the station appears dead, the supply to check is the one feeding the I/O base, not the adaptor. The housing material is Lexan and the protective treatment is TC.

Programming is done with the legacy Schneider Electric tool chain: Concept V2.6, Modsoft V2.5 or later, ProWORX NxT V2.0 or ProWORX 32. Confirm that your existing project and software version match before replacing an adaptor, because an M1 adaptor without a matching executive cannot run the program that the failed unit was running.

Operating ambient temperature is 0 to 60 °C, storage temperature is −40 to 85 °C, and relative humidity is 5 to 96 % without condensation. Operating altitude is up to 2000 m. Resistance to shock is 15 gn peak for 11 ms half sine wave and resistance to vibration is 1 gn at 0.75 mm double amplitude. The product is CE marked and certified UL, cUL, NEMA type 250 and FM Class 1 Division 2. Net weight is 0.042 kg; one piece is packed in a 260 x 180 x 60 mm carton of 0.219 kg.

Specifications

Characteristic Value
Range of product Modicon Momentum automation platform
Product or component type M1/M1E processor adaptor
Processor name x86 based (INTEL, AMD)
Clock frequency 20 MHz
Word length 16 bit
Memory type 256 kB flash, 64 kB RAM
Memory description Program memory 2.4 kB LL984, data 2 kB
Exact time for 1 K instruction 1 ms
Discrete I/O processor capacity 2048 I / 2048 O
Register I/O processor capacity 2048 I / 2048 O
I/O limit processor capacity I/O local on Modbus
Communication port protocol Modbus
Number of port 1 RS232C non isolated, 1 RS485
Rated supply voltage [Us] 5.0 V DC +/-5 %
Supply By Momentum I/O base
Software designation Concept V2.6, Modsoft >= V2.5, ProWORX NxT V2.0, ProWORX 32
Material Lexan
Protective treatment TC
Ambient air temperature for operation 0...60 °C
Ambient air temperature for storage −40...85 °C
Relative humidity 5...96 % without condensation
Operating altitude Up to 2000 m
Shock resistance 15 gn peak, 11 ms half sine wave
Vibration resistance 1 gn, 0.75 mm double amplitude
Marking CE
Product certifications UL, cUL, NEMA type 250, FM Class 1 Division 2
Net weight 0.042 kg
Packing unit weight 0.219 kg
Packing unit dimensions 260 x 180 x 60 mm