The 140DDO84300 is a DC discrete output module of the Schneider Electric Modicon Quantum automation platform. It has 16 discrete outputs in 2 groups of 8, with positive (source) output logic and a discrete output voltage of 10...60 V DC. Addressing requires 1 output word, and the module class is standard.
Output voltage limits are 10.2...72 V, and the absolute maximum output is a constant 72 V. Maximum voltage drop is less than 1 V at 2 A. Maximum load current is 12 A per module and 6 A per group, with a surge current of 7.5 A for 50 s. Response time is less than or equal to 1 ms from state 0 to state 1 and less than or equal to 1 ms from state 1 to state 0. Maximum leakage current is 1 mA at 60 V. Load inductance is given by inductance (H) = 0.5 / ((current (A))² x (switching frequency (Hz))).
Protection is by an internal output protection fuse of 8 A per group. Fuses used with relays are 2 A per point and 8 A per group. Insulation between each channel and the bus is 2500 Vrms DC for 1 minute, and insulation between groups is 700 Vrms DC for 1 minute. Marking is CE.
Power consumption is 1 W + (1 V x total module load current). Bus current requirement is 160 mA. Local signalling is 1 green LED for communication on the bus in progress (Active), 1 red LED for detected external fault (F), and 16 green LEDs for the output states.
Electrostatic discharge immunity is 4 kV on contact and 8 kV in air according to IEC 801-2, and immunity to electromagnetic fields is 10 V/m from 80 to 2000 MHz according to IEC 801-3. Operating temperature is 0...60 °C and storage temperature is -40...85 °C, with relative humidity of 95 % without condensation and operating altitude up to 5000 m. The module conforms to CSA C22.2 No 142 and UL 508, and product certifications are GOST, RMRS, FM Class I Division 2 and C-Tick.
Net weight is 0.45 kg. Packing unit 1 is 1 piece, 30.91 cm long, 16.33 cm wide and 4.73 cm high, with a packing weight of 452.6 g. Warranty is 18 months.
| Characteristic | Value |
|---|---|
| Brand | Schneider Electric |
| Range of product | Modicon Quantum automation platform |
| Product or component type | DC discrete output module |
| Number of discrete outputs | 16 |
| Channel configuration | 2 groups of 8 |
| Discrete output logic | Positive (source) |
| Discrete output voltage | 10...60 V DC |
| Output voltage limits | 10.2...72 V |
| Absolute maximum output | 72 V constant |
| Maximum voltage drop | < 1 V at 2 A |
| Maximum load current | 12 A per module; 6 A per group |
| Surge current | 7.5 A for 50 s |
| Response time | <= 1 ms, state 0 to state 1; <= 1 ms, state 1 to state 0 |
| Maximum leakage current | 1 mA at 60 V |
| Load inductance | Inductance (H) = 0.5 / ((current (A))² x (switching frequency (Hz))) |
| Protection type | Internal output protection, 8 A fuse per group |
| Fuse used with relay | 2 A per point; 8 A per group |
| Insulation between each channel and bus | 2500 Vrms DC for 1 minute |
| Insulation between groups | 700 Vrms DC for 1 minute |
| Addressing requirement | 1 output word |
| Power consumption | 1 W + (1 V x total module load current) |
| Bus current requirement | 160 mA |
| Module class | Standard |
| Marking | CE |
| Local signalling | 1 green LED for communication on the bus (Active); 1 red LED for detected external fault (F); 16 green LEDs for output states |
| Net weight | 0.45 kg |
| Electrostatic discharge immunity | 4 kV on contact, 8 kV in air, according to IEC 801-2 |
| Immunity to electromagnetic fields | 10 V/m, 80...2000 MHz, according to IEC 801-3 |
| Ambient air temperature for operation | 0...60 °C |
| Ambient air temperature for storage | -40...85 °C |
| Relative humidity | 95 % without condensation |
| Operating altitude | <= 5000 m |
| Standards | CSA C22.2 No 142; UL 508 |
| Product certifications | GOST; RMRS; FM Class I Division 2; C-Tick |
| Packing unit 1 type | PCE |
| Packing unit 1 quantity | 1 |
| Packing unit 1 length | 30.91 cm |
| Packing unit 1 width | 16.33 cm |
| Packing unit 1 height | 4.73 cm |
| Packing weight | 452.6 g |