The 140DDI35300 is a low voltage DC discrete input module for the Modicon Quantum automation platform. It reads 32 field signals per slot, arranged in four isolated groups of eight, and is intended for pushbuttons, limit switches, relay contacts and proximity sensors that switch a 24 V DC signal. Grouped isolation means a fault or noise on one group of eight does not disturb the other three.
Rated input voltage is 24 V DC with an operating range of 19.2...30 V. The guaranteed state 1 window is 15...30 V DC at a minimum of 2 mA, and the guaranteed state 0 window is -3...5 V DC at a maximum of 0.5 mA. Input impedance is 2500 Ω. Absolute maximum input is 30 V continuous, with a 56 V pulse decaying within 1.3 ms. The module uses positive logic with sink input, so the common terminal is connected to the positive potential and the field device pulls the input down.
Response time is 1 ms or less in both directions, from state 0 to 1 and from state 1 to 0. Insulation between groups is 500 Vrms for one minute, and between group and bus 1780 Vrms for one minute. The module occupies two input words of addressing and draws 330 mA from the rack bus.
Power dissipation is 1.7 W plus 0.36 W for every input that is switched on, which matters when sizing the rack power supply. Diagnostics are local: 32 green LEDs show the state of each input, one red LED reports an external fault, and one green LED shows bus communication activity. The module carries the CE mark and has no internal fuse; external fusing may be added at the user's discretion.
Operating temperature is 0...60 °C, storage -40...85 °C, relative humidity 95 % without condensation, and operating altitude up to 5000 m. Electrostatic discharge resistance is 4 kV by contact and 8 kV on air to IEC 801-2; electromagnetic field resistance is 10 V/m over 80...2000 MHz to IEC 801-3. The module meets CSA C22.2 No 142 and UL 508, and holds C-Tick, DNV, RINA, RMRS, BV, GOST and ABS certifications. Net weight is 0.3 kg; the single-unit package measures 30.97 × 16.45 × 4.65 cm and weighs 409.2 g.
| Characteristic | Value |
|---|---|
| Range of product | Modicon Quantum automation platform |
| Product or component type | Low voltage DC discrete input module |
| Discrete input number | 32 |
| Channel configuration | 4 groups of 8 inputs |
| Input logic | Positive (sink) |
| Discrete input voltage | 24 V DC |
| Input voltage limits | 19.2...30 V |
| Guaranteed state 1 voltage | 15...30 V DC |
| Guaranteed state 0 voltage | -3...5 V DC |
| Guaranteed state 1 current | ≥ 2 mA at Us = 5.5 V and Uin = 0 V |
| Guaranteed state 0 current | ≤ 0.5 mA |
| Input impedance | 2500 Ω |
| Absolute maximum input | 30 V continuous 56 V pulse decaying within 1.3 ms |
| Response time | ≤ 1 ms, state 0 to 1 ≤ 1 ms, state 1 to 0 |
| Input protection | By limited resistance |
| Address requirement | 2 input words |
| Bus current requirement | 330 mA |
| Power dissipation | 1.7 W + (0.36 W × number of inputs ON) |
| Insulation between groups | 500 Vrms for 1 minute |
| Insulation group to bus | 1780 Vrms for 1 minute |
| Local signalling | 32 green LEDs (input status 1...32) 1 red LED (external fault F) 1 green LED (bus communication activity) |
| Marking | CE |
| Module classification | Standard |
| Standards | CSA C22.2 No 142, UL 508 |
| Product certifications | C-Tick, DNV, RINA, RMRS, BV, GOST, ABS |
| Electrostatic discharge resistance | 4 kV contact, 8 kV on air (IEC 801-2) |
| Electromagnetic field resistance | 10 V/m, 80...2000 MHz (IEC 801-3) |
| Operating temperature | 0...60 °C |
| Storage temperature | -40...85 °C |
| Relative humidity | 95 % without condensation |
| Operating altitude | ≤ 5000 m |
| Net weight | 0.3 kg |
| Package size | 30.97 × 16.45 × 4.65 cm (L × W × H) |
| Package weight | 409.2 g |
| Contractual warranty | 18 months |
All values are taken from the Schneider Electric product datasheet for 140DDI35300. Module dimensions are shown in the datasheet dimension drawing: depth 103.9 mm for the module body, 144 mm including the terminal block.