The 140ACI04000C is the conformal-coated version of the 16-channel analog input module of the Modicon Quantum range. It is a current input module with three ranges on the same reference: 4...20 mA, 0...20 mA and 0...25 mA, which is what the multirange designation on the front of the product refers to. The inputs are differential, and addressing requires 17 input words. The electrical specification is the same as the standard reference; the difference is stated in the protective treatment field.
The protective treatment is Humiseal 1A33 conformal coating, a thin protective film applied over the assembled board and covering the solder joints and component leads. It is the reason this reference is specified where the standard version is not: it protects the board against moisture, salt mist, mould and corrosive gases that attack uncoated joints in service. On a panel where the standard reference is adequate, this version adds nothing electrically; on a panel where the atmosphere attacks the board, the standard reference is the wrong choice.
Resolution is quoted per range and per count format: 0...16000 counts on 4...20 mA, 0...20000 counts on 0...20 mA, 0...25000 counts on 0...25 mA, and 0...4095 counts on 4...20 mA. Wire-break detection is declared for the 4...20 mA range only, which is the practical reason to keep a live-zero range on a loop that has to be supervised. Input impedance is 250 ohm and the absolute maximum input is 30 mA. The wiring diagram carries one further limit that is easy to overlook: the maximum working voltage between channels must not exceed 30 Vdc.
Absolute accuracy error is ±0.125 % of full scale. Linearity error is a maximum of ±12 µA on 4...20 mA and a maximum of ±6 µA on 0...20 mA, 0...25 mA and the 0...4095-count 4...20 mA format. Temperature drift is ±0.0025 % of full scale per °C, with a second figure of 0.0050 % of full scale per °C or less. Common mode rejection is greater than −90 dB at 60 Hz. The input filter is a single-pole low-pass at −3 dB at 34 Hz ±25 %, and the update time is 15 ms for 2-wire and 4-wire connection.
Isolation between each channel and the bus is 1780 V AC for 60 s. Bus current requirement is 360 mA and power dissipation is 5 W, both of which have to be carried in the backplane power budget rather than assumed. The module classification is standard.
Diagnostics are on the front face: one green LED for bus communication activity, one red LED for an external fault, 16 green LEDs for channel on, and 16 red LEDs for channel fault, so a failed loop is identified at the channel rather than at the rack. The module carries the CE marking, is declared to UL 508 and CSA C22.2 No 142, and holds FM Class I Division 2 and cUL certification. Electrostatic discharge immunity is 4 kV on contact and 8 kV in air to IEC 801-2, and electromagnetic field immunity is 10 V/m from 80 to 1000 MHz to IEC 801-3.
Operating ambient air temperature is 0 to 60 °C, storage is −40 to 85 °C, relative humidity is 95 % without condensation, and operating altitude is up to 5000 m. Body dimensions are 290 mm high, 40.3 mm wide and 104 mm deep, or 144 mm deep with the field terminal block fitted. Net weight is 0.3 kg; one piece ships in a 310 x 165 x 48 mm carton of 450 g. Warranty is 18 months.
| Characteristic | Value |
|---|---|
| Range of product | Modicon Quantum |
| Product or component type | Analog input module |
| Protective treatment | Conformal coating Humiseal 1A33 |
| Number of analog inputs | 16 |
| Input type | Differential |
| Input ranges | 4...20 mA; 0...20 mA; 0...25 mA |
| Analog input resolution | 0...16000 counts on 4...20 mA; 0...20000 counts on 0...20 mA; 0...25000 counts on 0...25 mA; 0...4095 counts on 4...20 mA |
| Absolute maximum input | 30 mA |
| Input impedance | 250 ohm |
| Maximum working voltage between channels | 30 Vdc |
| Absolute accuracy error | ±0.125 % of full scale |
| Linearity error | ±12 µA max on 4...20 mA; ±6 µA max on 0...20 mA; ±6 µA max on 0...25 mA; ±6 µA max on 4...20 mA (0...4095 counts) |
| Temperature drift accuracy | ±0.0025 % of full scale per °C; ≤ 0.0050 % of full scale per °C |
| Common mode rejection | > −90 dB at 60 Hz |
| Filter type | Single-pole low-pass, −3 dB at 34 Hz ±25 % |
| Update time | 15 ms, 2-wire and 4-wire |
| Fault type | Wire break, 4...20 mA |
| Isolation between channel and bus | 1780 V AC for 60 s |
| Address requirement | 17 input words |
| Bus current requirement | 360 mA |
| Power dissipation | 5 W |
| Module classification | Standard |
| Local signalling | 1 green LED bus communication activity; 1 red LED external fault; 16 green LEDs channel on; 16 red LEDs channel fault |
| Marking | CE |
| Standards | UL 508; CSA C22.2 No 142 |
| Product certifications | FM Class I Division 2; cUL |
| Electrostatic discharge immunity | 4 kV contact, 8 kV air, per IEC 801-2 |
| Electromagnetic field immunity | 10 V/m, 80...1000 MHz, per IEC 801-3 |
| Dimensions (H x W x D) | 290 x 40.3 x 104 mm (144 mm with field terminal block) |
| Ambient air temperature for operation | 0...60 °C |
| Ambient air temperature for storage | −40...85 °C |
| Relative humidity | 95 % without condensation |
| Operating altitude | ≤ 5000 m |
| Net weight | 0.3 kg |
| Packing unit weight | 450 g |
| Packing unit dimensions | 310 x 165 x 48 mm |
| Warranty | 18 months |