140ACI04000 - Analog Input Module, 16 Inputs, Multirange, Modicon Quantum

Product type: Analog input module  |  Range: Modicon Quantum  |  Number of analog inputs: 16, differential  |  Ranges: 4...20 mA, 0...20 mA, 0...25 mA  |  Absolute accuracy: ±0.125 % of full scale  |  Update time: 15 ms  |  Address requirement: 17 input words  |  Bus current: 360 mA

The 140ACI04000 is a 16-channel analog input module of the Modicon Quantum range. It is a current input module with three selectable ranges on the same reference: 4...20 mA, 0...20 mA and 0...25 mA, which is what the multirange designation on the front of the product refers to. The inputs are differential. Addressing requires 17 input words.

Resolution is quoted per range and per count format: 0...16000 counts on 4...20 mA, 0...20000 counts on 0...20 mA, 0...25000 counts on 0...25 mA, and 0...4095 counts on 4...20 mA. Wire-break detection is declared for the 4...20 mA range only, which is the practical reason to keep a live-zero range on a loop that has to be supervised. Input impedance is 250 ohm and the absolute maximum input is 30 mA. The wiring diagram carries one further limit that is easy to overlook: the maximum working voltage between channels must not exceed 30 Vdc.

Absolute accuracy error is ±0.125 % of full scale. Linearity error is a maximum of ±12 µA on 4...20 mA and a maximum of ±6 µA on 0...20 mA, 0...25 mA and the 0...4095-count 4...20 mA format. Temperature drift is ±0.0025 % of full scale per °C, with a second figure of 0.0050 % of full scale per °C or less. Common mode rejection is greater than −90 dB at 60 Hz. The input filter is a single-pole low-pass at −3 dB at 34 Hz ±25 %, and the update time is 15 ms for 2-wire and 4-wire connection.

Isolation between each channel and the bus is 1780 V AC for 60 s. Bus current requirement is 360 mA and power dissipation is 5 W, both of which have to be carried in the backplane power budget rather than assumed. The module classification is standard.

Diagnostics are on the front face: one green LED for bus communication activity, one red LED for an external fault, 16 green LEDs for channel on, and 16 red LEDs for channel fault, so a failed loop is identified at the channel rather than at the rack. The module carries the CE marking, is declared to UL 508 and CSA C22.2 No 142, and holds FM Class I Division 2 and cUL certification. Electrostatic discharge immunity is 4 kV on contact and 8 kV in air to IEC 801-2, and electromagnetic field immunity is 10 V/m from 80 to 1000 MHz to IEC 801-3.

Operating ambient air temperature is 0 to 60 °C, storage is −40 to 85 °C, relative humidity is 95 % without condensation, and operating altitude is up to 5000 m. Body dimensions are 290 mm high, 40.3 mm wide and 104 mm deep, or 144 mm deep with the field terminal block fitted. Net weight is 0.3 kg; one piece ships in a 310 x 165 x 46 mm carton of 433 g. The product is declared RoHS compliant, with a China RoHS declaration. Warranty is 18 months.

Specifications

Characteristic Value
Range of product Modicon Quantum
Product or component type Analog input module
Number of analog inputs 16
Input type Differential
Input ranges 4...20 mA; 0...20 mA; 0...25 mA
Analog input resolution 0...16000 counts on 4...20 mA; 0...20000 counts on 0...20 mA; 0...25000 counts on 0...25 mA; 0...4095 counts on 4...20 mA
Absolute maximum input 30 mA
Input impedance 250 ohm
Maximum working voltage between channels 30 Vdc
Absolute accuracy error ±0.125 % of full scale
Linearity error ±12 µA max on 4...20 mA; ±6 µA max on 0...20 mA; ±6 µA max on 0...25 mA; ±6 µA max on 4...20 mA (0...4095 counts)
Temperature drift accuracy ±0.0025 % of full scale per °C; ≤ 0.0050 % of full scale per °C
Common mode rejection > −90 dB at 60 Hz
Filter type Single-pole low-pass, −3 dB at 34 Hz ±25 %
Update time 15 ms, 2-wire and 4-wire
Fault type Wire break, 4...20 mA
Isolation between channel and bus 1780 V AC for 60 s
Address requirement 17 input words
Bus current requirement 360 mA
Power dissipation 5 W
Module classification Standard
Local signalling 1 green LED bus communication activity; 1 red LED external fault; 16 green LEDs channel on; 16 red LEDs channel fault
Marking CE
Standards UL 508; CSA C22.2 No 142
Product certifications FM Class I Division 2; cUL
Electrostatic discharge immunity 4 kV contact, 8 kV air, per IEC 801-2
Electromagnetic field immunity 10 V/m, 80...1000 MHz, per IEC 801-3
Dimensions (H x W x D) 290 x 40.3 x 104 mm (144 mm with field terminal block)
Ambient air temperature for operation 0...60 °C
Ambient air temperature for storage −40...85 °C
Relative humidity 95 % without condensation
Operating altitude ≤ 5000 m
RoHS EU RoHS compliant; China RoHS declaration
Net weight 0.3 kg
Packing unit weight 433 g
Packing unit dimensions 310 x 165 x 46 mm
Warranty 18 months