The 2080-MOT-HSC from Allen Bradley is a highly efficient high-speed counter plug-in module specifically designed for the Micro 800 series. This module effectively processes quadrature differential input signals across a full voltage range of 0 to 30 V DC, with a maximum input frequency of 250 kHz under standard operational conditions.
| Manufacturer | Allen Bradley |
|---|---|
| Product Type | High-speed counter plug-in module |
| Product Line | Micro 800 |
| Part Number | 2080-MOT-HSC |
| Weight | 0.19 lbs (0.09 kg) |
| Input Type | Quadrature differential (A, B, Z) channels |
| Number of Inputs | 1 channel (ABZ) |
| Input Voltage Range | 0 – 30 V DC |
| Input Current Range | 2 – 9 mA typical |
| Input Frequency (Max) | 250 kHz (50 % duty cycle) |
| Input Impedance (Nominal) | 3.58 kΩ |
| Minimum Pulse Width | 2 µs |
| Output Channels | 1 physical + 15 virtual |
| Output Voltage Range | 5 – 30 V DC |
| Output Current (Max) | 0.5 A per output |
| Output Switching Time | ≤ 2 ms on/off |
| Bus Power Draw | 60 mA @ 3.3 V DC |
| Isolation Voltage | 50 V continuous (tested @ 720 V DC for 60 s) |
The Allen Bradley 2080-MOT-HSC is categorized as a high-speed counter plug-in module, vital for the Micro 800 series applications. It accommodates quadrature differential input configurations through its single channel designated as ABZ. The operational input voltage maintains a range between 0 to 30 V DC, ensuring compatibility with various devices. Typical input currents are maintained between 2 to 9 mA, aligning with the system requirements.
This module excels in managing an input frequency of up to 250 kHz, maintaining a duty cycle of 50%. It also features an input impedance nominally rated at 3.58 kΩ and supports pulse widths as brief as 2 µs. Regarding output capabilities, the 2080-MOT-HSC provides one physical output channel alongside an extensive array of 15 virtual outputs. User settings are permissible within an output voltage range of 5 to 30 V DC, and outputs can handle a maximum current of 0.5 A. The switching time for output signals is quick, recorded at 2 milliseconds or less.
Power draw from the bus is noted at 60 mA, operating at 3.3 V DC. For safety, the module includes an isolation voltage rated at 50 V for continuous use and has been rigorously tested at 720 V DC for a duration of 60 seconds, confirming its reliability in demanding environments.