Manufacturer | Rockwell Automation |
Brand | Allen-Bradley |
Part Number/Catalog No. | 1734-OW4 |
Manufacturer | Rockwell Automation |
Series | POINT I/O |
Brand | Allen-Bradley |
Module Type | Digital Contact Module |
Series | POINT I/O |
Outputs | 4 N.O relay |
Product Description | Four (4) channel Relay output module |
POINTBus Current | 80 milliamps |
No. of outputs | Four (4) Normally Open (N.O.) contact outputs |
Power Dissipation, Max | 0.5 Watts |
Output delay time, on to off, max | 26 ms |
Thermal Dissipation | 1.7 BTU/hour |
Contact resistance, initial | 30 m? |
UPC | 10612598309846 |
Leakage current, off-state output, max | 1.2 mA and bleed resistor through snubber circuit @ 240V AC |
Power dissipation, max | 0.5 W |
Thermal dissipation, max | 1.7 BTU/hr |
Terminal Base | 1734-TB, 1734-TBS, 1734-TOP, or 1734-TOPS |
Mounting type | DIN Rail |
Enclosure | None (open-style) |
Operating temperature | -20…55 degrees C (-4…131 degrees F) |
Nonoperating temperature | -40…85 degrees C (-40…185 degrees F) |
Are the contact outputs isolated from each other on this Digital Contact Module?
Yes, the contact outputs are isolated from each other on the 1734-OW4 POINT Digital Contact Module.
Do I need to configure the 1734-OW4 Digital Contact module to match the baud rates of existing devices on the network?
No, 1734-OW4 Digital Contact Module has an auto-baud feature, which automatically matches the baud rate of existing devices on the network. Therefore, no manual configuration is necessary.
What is the price of 1734-OW4 POINT Digital Contact Module?
Submit a quote request, send us an email for our best price.
Where can I find repair services for the 1734-OW4 POINT Digital Contact Module?
offers repair services for the 1734-OW4 POINT Digital Contact Module. For more information or to request a repair quote, please contact us.
1. What is the output contact from of the 1734-OW4?
The 1734-OW4 has Four (4) Normally Open (N.O.) contacts
2. What are compatible wiring base assemblies for use with the 1734-OW4?
The 1734-OW4 requires use of 1734-TB, 1734-TBS, 1734-TOP, or 1734-TOPS terminal base.
3. Does the 1734-OW4 capable of acting as distributed I/O component of ControlLogix PLC?